TeSys GV motor circuit breaker, 3 poles (3P), 1.6A/690V, for 3-phase motor applications 0.37-0.55kW@400V. It provides a thermal-magnetic protection with a thermal setting range 1-1.6A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).

Specifications Source: Schneider Electric product page
Product or component typeMotor circuit breaker
Device short nameGV2ME
Device applicationMotor protection
Trip unit technologyThermal-magnetic
Poles description3P
Network typeAC
Utilisation category
  • Category A conforming to IEC 60947-2
  • AC-3 conforming to IEC 60947-4-1
  • AC-3e conforming to IEC 60947-4-1
Network frequency50/60 Hz conforming to IEC 60947-2
Motor power kW
  • 0.37 kW at 400/415 V AC 50/60 Hz
  • 0.55 kW at 400/415 V AC 50/60 Hz
  • 0.37 kW at 500 V AC 50/60 Hz
  • 0.55 kW at 500 V AC 50/60 Hz
  • 0.75 kW at 500 V AC 50/60 Hz
  • 0.75 kW at 690 V AC 50/60 Hz
  • 1.1 kW at 690 V AC 50/60 Hz
Breaking capacity
  • 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
  • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control typePush-button
[In] rated current1.6 A
Thermal protection adjustment range1…1.6 A conforming to IEC 60947-2
Magnetic tripping current26.2 A
[Ith] conventional free air thermal current1.6 A conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-2
Phase failure sensitivityYes conforming to IEC 60947-4-1
Suitability for isolationYes conforming to IEC 60947-1
Power dissipation per pole2.5 W
Mechanical durability100000 cycles
Electrical durability
  • 100000 cycles for AC-3 at 415 V In
  • 100000 cycles for AC-3e at 415 V In
Rated dutyUninterrupted conforming to IEC 60947-4-1
Connections - terminals
  • Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid
  • Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end
  • Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
Tightening torque1.7 N.m - on screw clamp terminal
Fixing mode
  • 35 mm symmetrical DIN rail: clipped
  • Panel: screwed (with adaptor plate)
Mounting position
  • Horizontal
  • Vertical
Width45 mm